ZFP fixed powder fire extinguishing device

Product specifications: ZFP150, ZFP250, ZFP500, ZFP750, ZFP1000, ZFP2000, ZFP3000

  • Details
  • Parameter
Products real shot

product description

ZFP automatic dry powder fire extinguishing system is an important equipment for fire extinguishing systems in projects such as petrochemical, oil tankers, oil depots, gas stations, ports and docks. The dry powder fire extinguishing system uses nitrogen as a power source, provides pressure in the relevant sub-tanks, pushes the dry powder fire extinguishing agent in the dry powder tank, and transports it to the dry powder cannon, dry powder gun or fixed nozzle through pipelines to spray out, so as to achieve the purpose of extinguishing flammable and combustible liquids, combustible gases and electrical equipment fires.

1. System composition

The ZFP automatic dry powder fire extinguishing system consists of a starting bottle, a nitrogen bottle group, a decompression method, a dry powder tank, a dry powder gun, a dry powder cannon, a fixed dry powder nozzle, an electric control cabinet, valves and pipelines and other components.

2. Main features

ZFP automatic dry powder fire extinguishing system can be used for four types of fire: A, B, C, and D. Its main features are as follows:

It has high fire extinguishing efficiency and is especially suitable for fires involving petroleum products.

It has good insulation properties and can be used to extinguish fires in live equipment.

No antifreeze is needed in cold areas and it can be used in water-scarce areas.

Dry powder fire extinguishing agent will not deteriorate during long-term storage.

3. Working principle

The working principle of the ZFP dry powder fire extinguishing system is as follows: the high-pressure nitrogen in the nitrogen cylinder group is decompressed by the pressure reducing valve, and then the nitrogen enters the dry powder tank, and a part of it is sent to the bottom of the tank, which plays the role of loosening the dry powder fire extinguishing agent. As the pressure in the tank increases, part of the dry powder fire extinguishing agent enters the powder outlet pipe with the nitrogen and is sent to the outlet valve of the dry powder cannon, dry powder wall or dry powder fixed nozzle. When the pressure at the outlet valve of the cannon, gun or dry powder fixed nozzle reaches a certain value (the pressure value on the dry powder tank reaches 1.5~1.6Mpa), open the valve (or the constant pressure bursting diaphragm automatically bursts), and the pressure energy is quickly converted into speed energy. In this way, the high-speed gas powder flow is ejected from the nozzle of the dry powder cannon (or dry powder gun, fixed nozzle), shot at the fire source, cut the flame, destroy the combustion chain, and play a role in quickly extinguishing or suppressing the fire.

Parameter configuration

model

ZFP50

ZFP100

ZFP150

ZFP200

ZFP300

ZFP500

ZFP750

ZFP1000

ZFP2000

ZFP3000

Dry powder tank

Storage capacity (kg)

50

100

150

200

300

500

750

1000

2000

3000

Working pressure (MPa)

1.6

Residual powder rate (%)

≤15

N2 bottle set

Quantity (bottle, 40L)

1

2

0

Quantity (bottle, 70L)

0

0

2

3

4

8

12

Filling pressure (20℃MPa)

15

Dry powder gun

Working pressure (MPa)

1.0~1.6

Injection rate (kg/s)


10~20

30~50

Tolerance: ±8%

Range (m)






≥15~25

≥35~55

Pressure reducing valve

quantity

1

2

3

Working pressure (MPa)

1.6±0.1

Dry powder nozzle

Model

DC

Diffusion

Fan type

Working pressure (MPa)

0.3~1.6

Injection rate (kg/s)

1~3

Tolerance: ±8%

Dry powder delivery pipe

Require

The total capacity of the connections shall not exceed 30% of the volume of the dry powder tank; the number of main pipe elbows shall generally not exceed 4.

Maximum horizontal distance (m)


≤4

≤8

Maximum vertical distance (m)


≤5

≤10