Automatic Tracking and Location Fire Extinguishing System (Foam Cannon)

  • Details
  • Parameter
Product Shooting
Product Introduction

Function Introduction
Equipped with video assist function, the system can achieve remote manual positioning and fire confirmation through the video management system.

Can be self/manual controlled through the video management system or on-site control box:

Automatic mode:
After the device is positioned, an alarm signal is sent, and the matching equipment such as electromagnetic valves and water pumps are linked to spray water to extinguish the fire. After the fire is extinguished, the electromagnetic valve and water pump are automatically shut off. If there is a re-ignition, all actions are repeated.

Manual mode:
After the device is positioned, an alarm signal is sent. At this time, it is required to transmit the on-site image to the fire department through the on-site control box or the camera inside the device to confirm the fire situation. The equipment can be manually operated to adjust horizontally/vertically and reset. The application of this technology avoids the damage to valuable items on site caused by water spray when the fire is under human control.

The fire extinguishing device can be manually controlled to rotate horizontally/vertically, open the valve, and start the pump through the on-site control box, and is equipped with an emergency stop button to cut off the power in case of emergencies.

The sensitivity can be adjusted and different sensitivity levels can be used in different places.

The product is equipped with a power supply, communication surge module, which can effectively prevent lightning damage to the product.

Parameter configuration:

Installation height: 8~15m
Maximum protection radius: 50m
Maximum flow rate: 20L/s
Rated working pressure: 0.8Mpa
Maximum working pressure: 1Mpa
Interface diameter: DN80
Working voltage/power consumption: AC220V/monitoring: 1W, scanning: 50W
Communication mode: RS485 (communication with on-site control box)
Fire response time: ≤30S
Operating environment temperature: 4~55℃
Horizontal rotation range: 0~360°
Vertical rotation range: pitch angle 30°, yaw angle 90°
Dimensions: 290*230*360mm